In any Smart Instrumentation module, select Tools > Interfaces > Honeywell.
-
On the Honeywell Interface dialog, under Data transfer mode, select Publish Smart Instrumentation data, and then select OK.
-
On the Plant Controller Selection dialog, do one of the following:
-
To publish all relevant database fields for Honeywell Experion PKS , select the Select all check box.
-
For publishing of data associated with a given controller, select the Select check box next to that controller.
-
-
On the Publish to File dialog, under Folder to save XML files, type the path for Honeywell Experion PKS publishing.
-
Select OK to publish the .xml file for the first controller that you selected.
-
For each additional controller that you selected in the Smart Instrumentation Plant Controller Selection dialog, when the Publish to File dialog reopens, select OK.
-
Smart Instrumentation publishes the data associated with each controller into a separate .xml file.
-
On publishing data other than for the first time, Honeywell Experion PKS identifies changes as follows:
-
The software identifies new items created in Smart Instrumentation as new items to be created in Honeywell.
-
If you move items, cards, CS tags, or if you modify item fields in Smart Instrumentation, the software identifies these as items to be updated in Honeywell.
-
The software identifies items deleted in Smart Instrumentation as items to be deleted in Honeywell.
-