On this form you enter the required data according to the fields that are available. Certain fields allow for the entering of alpha-numeric values, while others require you to select a value from a list. Depending on the value you choose from a list, further fields become available for data entry.

For more information on the Data Entry Calibration Form and its various sections, see Standard Data Entry Calibration Form.

  1. In the Tag Calibration Settings window, select Actions > Data Entry PPM All Outputs Graphic.

  2. If required, in the Codes section do the following:

    • From the Result code list, select the required predefined result code, or custom result code predefined in the Result Code dialog.

    • From the Action code list, select an action code if required.

    • From the Diagnostic code list, select a diagnostic code if required.

    • From the Damage code list, select a damage code if required.

    SHARED Tip If a required result, diagnostic, damage, or action code is not available from the list, you can define additional codes by selecting the appropriate item on the Tables menu.

  3. In the Set point section enter any required values.

    • Type the pre-calibration values in the As Found column. On the standard calibration data entry page in the Results Points section, error values that exceed the maximum permissible error are highlighted in red, while values that exceed the intermediate error tolerances but do not exceed the permissible error are highlighted in light blue.

    • After calibration of the instrument, type the values in the As Left column. Any error values still highlighted in red, in the Results Points section, show that this instrument's calibration failed. When you save the updated data, the software prompts you to create a Work Request. For details, see Performing Breakdown Maintenance.

  4. In the Alarms / Trips section, enter the data for the First, Second, Third, Fourth, Fifth, or Sixth Point if required.

  5. If required in other available fields, type the required value, or select a value from the list.

    SHARED Tip In the Results Points section, you can enter or modify As Found and As Left calibration values and view calibration results for a selected instrument.

  6. Select SaveSave Icon 16bit.

  7. To browse through the tags that you selected, select Previous icon 16bit or Next icon 16bit.

  • Errors are calculated to four decimal places. Any error smaller than 0.0001 will be displayed as zero (0) and stored in the database as zero.

  • The fields cmpnt_mfr_id and cmpnt_mod_id display the current manufacturer and model name associated with the tag. The fields cmpnt_mfr_name and cmpnt_mod_name display the history of changes made to the manufacturer and model name when saving the Calibration Data Entry sheet.