Environmental Factor - TANK - Help - Hexagon PPM

TANK Help

Language
English
Product
TANK
Subproduct
TANK
Search by Category
Help

Defines the environmental factor according to Table 9 of API- 2000.

English Units:

Configuration

Conductance (BTU/hr ft2 F)

Insulation Thickness (in)

F Factor

Bare metal tank

---

0

1.0

Insulated tank

4.0

1

0.3

Insulated tank

2.0

2

0.15

Insulated tank

1.0

4

0.075

Insulated tank

0.67

6

0.05

Insulated tank

0.50

8

0.375

Insulated tank

0.40

10

0.300

Insulated tank

0.33

12

0.025

Concrete or Fireproofing

---

---

see note C

Water-application facilities

---

---

1.0

Depressuring and emptying

---

---

1.0

Underground Storage

---

---

0.0

Earth-covered storage above Grade

---

---

0.03

Impoundment away from tank

---

---

0.5

Metric Units:

Configuration

Conductance (Watts/m2 K)

Insulation Thickness (cm)

F Factor

Bare metal tank

---

0

1.0

Insulated tank

22.7

2.5

0.3

Insulated tank

11.4

5

0.15

Insulated tank

5.7

10

0.075

Insulated tank

3.8

15

0.05

Insulated tank

2.8

20

0.375

Insulated tank

2.3

25

0.300

Insulated tank

0.19

30

0.025

Concrete or Fireproofing

---

---

see note C

Water-application facilities

---

---

1.0

Depressuring and emptying

---

---

1.0

Underground Storage

---

---

0.0

Earth-covered storage above Grade

---

---

0.03

Impoundment away from tank

---

---

0.5